MSE Of Canada Ltd.
MARINE SAFE ELECTRONICS OF CANADA LIMITED has seventeen years
experience in the design, manufacture and world wide marketing
of insulation monitors for electric motors, generators and
airport lighting circuits. All design is done in Canada.
Manufacturing is done in-house or by subcontractors. Promotion
and sales are by appointed representatives throughout the world.
MotoSafe(tm) and FailSafe(tm) Insulation Monitors are engineered
for industrial and marine applications respectively. They carry
UL Listing, CSA certification, Lloyds Type approval by the
American Bureau of Shipping, the US Coast Guard, DET Norske
Veritas and Germanisher Lloyd. Units for airport lighting
circuit monitoring meet FAA requirements.
MotoSafe(tm) and FailSafe(tm) Insulation Monitors give early
warning of electrical insulation deterioration, to permit timely
preventive maintenance to restore the insulation to its 'as
new' condition. Installable for alarm only or for start
prevention, as required, bypass is provided by selectable alarm
levels on most models.
All units are designed for DIN rail mounting and have shrouded,
front accessible terminals for all wiring. Units are available
for all standard AC voltages to 6.6 kV and for DC voltages to
1200 v.
MotoSafe(tm) and FailSafe(tm) Insulation Monitors are sold to
all sectors, with emphasis on the marine, mining, pulp and paper,
petroleum and industrial markets.
Company Details
Year Established:
1978
Total Sales ($CDN):
$100,000 - $200,000
Number of Employees:
5
Company Information
Jeffrey Khan
Title:
Vice President
Telephone:
(905) 738-3744
Fax:
(905) 738-5732
Email:
Click Here
Zarah Dehnashi
Title:
Administrator
Telephone:
(905) 738-3744
Fax:
(905) 738-8732
Email:
Click Here
Arie Lasker
Title:
Vice President
Area of Responsibility:
Research/Development/Engineering
Telephone:
(905) 738-3744
Fax:
(905) 738-5732
Email:
Click Here
Products
Insulation Monitors, Electric Motor
Insulation Monitors, Large Electric Motor
MotoSafe(tm) Insulation Monitor Model LM602IND is used on large
motors with a maximum line voltage of 600 v AC/DC, to give early
warning of insulation deterioration to 5 or 2.5 MQ. Control
voltage 400 v AC, 50/60 Hz, isolation voltage 24-300 volts,
AC/DC, sensing voltage 400 v DC. DIN rail mounting. Alarm
contact rating 5 amps, 250 v AC resistive. Size (WxHxL) is 103
x68x112 mm, weight 0.42 kg.
Insulation Monitors, Generator And Motor
The MotoSafe(tm) Insulation Monitor Model LM600IND is used on
generators and motors with a maximum line voltage of 600 v AC/DC
to give a meter reading of insulation resistance and early
warning of insulation deterioration to 2 MQ. Control voltage 120
or 220 v AC, 50/60 HZ, isolation voltage 24-300 volts, AC/DC,
sensing voltage 24 v DC. DIN rail mounting. Alarm contact
rating 5 amps, 250 v AC resistive. Size (WxHxL) 103x68x112 mm,
weight 0.42 kg.
Insulation Monitors, Motors & Generators To 13,800v
The MotoSafe(tm) Insulation Monitor Type MHV is used on motors
and generators to 13,800 volts AC to give early warning of
insulation deterioration to 5 or 2.5 MQ. Model MHV uses 24 v DC
sensing and Model MHV-H uses a 400 volt DC sensing. Selection
depends on personal preference, the insulation has lost its
dielectric strength when an alarm occurs. Control voltage
120 v AC, 50/60/ Hz, isolation voltage 24-300 volts, AC/DC. DIN
rail mounting. Alarm contact rating 5 amps, 250 v AC resistive.
Size (WxHxL) 103x68x112 mm, weight 0.42 kg. Requires and
Intermediate Resistor Block for connection.
Resistor Blocks, Electric Motor
The MotoSafe(tm) Intermediate Resistor Block is used to connect
Model MHV and Model MHV-M units to the monitored motor. Not
sold separately, shiped as part of the units. Dielectric
strength 17 kV AC, 1 minute, 32 kV AC 1 second. Size (HxWxL)
180x112x60 mm, weight 2,23 kg.
Circuit Monitors, Airport Lighting
The MotoSafe(tm) Airport Lighting Circuit Monitor Type ALC is
available for 1.5 kV and 3 kV AC regulator output voltages.
Units for 3 and 4.5 kV consist of Model ALC-M monitor with Model
ALC-1U interface unit. Control voltage 120 or 220 v AC, 50/60
Hz, isolation voltage 24-300 volts, AC/DC, sensing 24 v DC.
DIN rail mounting. Alarm contact rating 5 amps, 250 v AC
resistive. Model ALC-M size (WxHxL) 103x68x112 mm, weight 0.42
kg. Model ALC-1U size (WxLxL) 55x68x112 mm.
Predictive Maintenance Systems
Instrumentation
Insulation Monitor, 24v Dc Ungrounded Control Systems
The FailSafe(tm) Insulation Monitor Model CVM-DC is used in ships
or industry with a line voltage of 24V D.C. to give early warning
of insulation deterioration from 1,0.5&0.25MQ. Control voltage
derived from line voltage, power requirements 3 w., contact
rating 5 amp., 250v. AC resistive. DIN rail mounting. Size
(WxHxL) 45x68x112mm, weight 0.27 kg.
Insulation Monitors, 120v A.C. Single Phase Control Power Systems
The FailSafe(tm) Insulation Monitor Model CVM-AC is used in ships
or industry with a line voltage of 120V A.C. 1 phase to give
early warning of insulation deterioration from 1,0.5& 0.25MQ.
Control voltage derived from line voltage, power requirements 3
va., contact rating 5 amp., 250v. AC resistive. DIN rail
mounting. Size (WxHxL) 45x68x112 mm, weight 0.27 kg.
Insulation Monitors, Three Phase Power Systems
The FailSafe(tm) Insulation Monitor Model USM120 is used in ships
with a line voltage of 120AC, 3 phase to give early warning of
insulation deterioration from 1,0.5&0.25MQ. Control voltage
derived from line voltage, power requirements 3 va., contact
rating 5 amp., 250v. AC resistive. DIN rail mounting. Size
(WxHxL) 45x68x112 mm, weight 0.27 kg.
Insulation Monitor, Electrical Machines
The FailSafe(tm) Insulation Monitor Model MGM600D is for use in
ships with a max. line voltage of 600 AC/DC to give early warning
of insulation deterioration from 3,1&0.5 MQ. Control voltage
115/220v. AC, 50/60 Hz, Isolation voltage 100-600v. AC/DC, power
requirements 3 va., contact rating 5 amp., 250v. AC resistive.
DIN rail mounting. Size (WxHxL) 45x68x112 mm, weight 0.27 kg.
Insulation Monitor, Low Voltage Dc.Ac Electrical Machines
The FailSafe(tm) Insulation Monitor Model M1200 is used to
monitor Low Voltage DC/AC motor installations for insulation
deterioration whenever they are not energized with a line voltage
of 1,200 DC; 1,000 AC. to give early warning of insulation
deterioration from 5.0 to 2.5 MQ. Control voltage 120 or 220,
50/60 Hz, Control power 3 va., Isolation votage 24-300 AC/DC,
contract rating 5 amp., 250v. AC resistive. DIN rail mounting.
Size (WxHxL) 103x68x112 mm, weight 0.42 kg.
Services